Program-related Functions
Reset Operation =
Fixed SP Operation
Set point
Segment 0
100.0
50.0
PV at startup
0.20
= 20.0
• If there is an input error when operation starts and the segment type of
segment 0 is set to ramp or step, the program will start from the SP of
segment 0. If the segment type of segment 0 is soak, reset status will be
entered.
Program operation will start from the fixed SP (FSP) or remote SP (RSP).
A setting example is shown below. The Time Unit of Ramp Rate parameter is
set to minutes.
Segment No.
Segment Type (styp)
Segment Set Point (sp)
Segment Rate of Rise
(pr)
Segment Time (h.min)
(time)
Set point
Segment 0
100.0
50.0
Fixed SP =
0.20
20.0
• If the SP Mode parameter is set to Remote SP Mode, there is an RSP
input error when operation starts, and the segment type of segment 0 is
set to ramp or step, the program will start from the SP of segment 0. If the
segment type of segment 0 is soak, reset status will be entered.
Segment 1
0.40
0
Ramp
Soak
100.0
---
4.0
---
---
0.40
Segment 1
0.40
Section 4-15
Segment 2
0.20
Time (h.min)
1
2
Ramp
50.0
2.5
---
Segment 2
0.20
Time (h.min)