Initial Setting Level
sl-h
SP Upper Limit
sl-l
SP Lower Limit
Function
Setting
See
See
cntl
PID ON/OFF
Function
Setting
See
See
238
• These parameters set the upper and lower limits of the set points. A set
point can be set within the range defined by the upper and lower limit set
values in the SP Upper Limit and SP Lower Limit parameters. If these
parameters are reset, any set point that is outside of the new range will be
forcibly changed to either the upper limit or the lower limit.
• When the temperature input type and temperature unit have been
changed, the set point upper limit and set point lower limit are forcibly
changed to the upper and lower limits of the sensor.
• During temperature input, the decimal point position depends on the cur-
rently selected sensor, and during analog input it depends on the Decimal
Point parameter setting.
Controllers with Universal Thermocouple/Resistance Thermometer/Analog
Inputs
Parameter
name
Set Point
Temperature
Upper Limit
Analog
Set Point
Temperature
Lower Limit
Analog
■ Related Parameters
Input type: Page 236, Temperature unit: Page 237 (initial setting level)
• This parameter selects 2-PID control or ON/OFF control.
• Auto-tuning can be used for 2-PID control.
Setting range
pid: 2-PID, onof: ON/OFF
■ Related Parameters
AT execute/cancel: Page 208, Manual reset, Hysteresis (heating), and Hyster-
esis (cooling): Page 218 (adjustment level)
Setting range
SP lower limit + 1 to Input set-
ting range upper limit
SP lower limit + 1 to scaling
upper limit
Input setting range lower limit
to SP upper limit
1
Scaling lower limit to SP
upper limit
1
Default
pid
Section 5-9
Unit
Default
EU
1300.0
EU
EU
200.0
EU