Advanced Function Setting Level
out2
Control Output 2 Assignment
Function
Setting
See
See
274
• This parameter sets the function to be assigned to control output 2.
none: No function is assigned to control output 2.
o:
Heating control output is output.
c-o:
Cooling control output is output. (See note 1.)
alm1: Alarm 1 is output. (See note 2.)
alm2: Alarm 2 is output. (See note 2.)
alm3: Alarm 3 is output. (See note 2.)
p.end: Program end is output. (See note 2.)
ralm: Control output ON/OFF count alarm (See note 2.)
stg:
Stage output (See note 2.)
run:
Run output (See note 2.)
ts1:
Time signal 1 output (See note 2.)
ts2:
Time signal 2 output (See note 2.)
wr1:
Work bit 1 (See notes 2 and 3.)
wr2:
Work bit 2 (See notes 2 and 3.)
wr3:
Work bit 3 (See notes 2 and 3.)
wr4:
Work bit 4 (See notes 2 and 3.)
wr5:
Work bit 5 (See notes 2 and 3.)
wr6:
Work bit 6 (See notes 2 and 3.)
wr7:
Work bit 7 (See notes 2 and 3.)
wr8:
Work bit 8 (See notes 2 and 3.)
(1) If c-o is assigned for standard control, a value equivalent to 0% will be
Note
output.
(2) Can be selected for a relay output, voltage output (for driving SSR) only.
(3) WR1 to WR8 are not displayed when the logic operation function is not
used.
(4) If the Standard or Heating/Cooling parameter is set to heating/cooling
control, control automatically switches to c-o.
■ Related Parameters
Standard or heating/cooling: Page 239 (initial setting level)
There must a transfer output, or if
there is no transfer output, control
output 1 must be a linear output or
control output 2 must not be a linear
output. If control output 1 is not a lin-
ear output and control output 2 is a
linear output, the transfer output type
must be set to OFF.
Setting range
Section 5-10
Default
none
(See note
5.)