Wiring Terminals
CT Inputs
14
15
E53-CN@H@N2
(for E5CN-HT)
Transfer Output
38
Polarities during no-contact input are as follows:
11
EV1
12
+
EV2
13
+
Two Event Inputs:
E53-CN@B@N2
(for E5CN-HT)
• When the HB alarm, HS alarm, or heater overcurrent alarm is to be used
with the E5CN-HT@M@-500 with an E53-CN@H/HH@N2 Option Unit,
connect a current transformer (CT) across terminals 14 and 15 or termi-
nals 13 and 15 (no polarity).
• When the HB alarm, HS alarm, or heater overcurrent alarm is to be used
with the E5AN/EN-HT@@H@-500 or E5AN/EN-HT@@HH@-500, connect
a current transformer (CT) across terminals 14 and 15 or terminals 15
and 16 (no polarity).
13
14
CT
CT1
15
E53-CN@HH@N2
• On the E5CN-HT@M@-500 with an E53-CN@FN2, the transfer output is
output across terminals 14 and 15.
• On the E5AN/EN-HT@@F-500, transfer output is output across terminals
27 and 28.
E53-CN@FN2
(for E5CN-HT)
Output type
Current
Even with models that do not have a transfer output, control outputs 1 or 2 can
be used as a simple transfer output if it is a current output or linear output. For
details on the operation, refer to 4-13 Using the Transfer Output.
11
+
EV1
12
+
EV2
13
Two Event Inputs:
E5AN/EN-
HT@B@M@-500
(for E5AN/EN-HT)
14
CT2
15
E5AN/EN-HT@@H@-500
v
+
+
14
L
15
Current
E5AN/EN-HT@@F-500
Specifications
4 to 20 mA DC, Load: 600
Section 2-2
23
+
EV3
24
+
EV4
25
Two Additional Event Inputs:
E53-AKB in E5AN/EN-
HT@B@M@-500
(for E5AN/EN-HT)
14
15
CT
16
E5AN/EN-HT@@HH@-500
v
+
+
27
L
28
Current
max., Resolution: 10,000
CT1
CT2