Starting Control Operation
The E5jJ will start control operations as soon as power is turned on
until power is turned off. Turn off the power and then turn it back on
after setting the desired parameters.
By short-circuiting the EV2 terminals (terminals 17 and 19) of the
E5AJ/E5EJ incorporating event input, control operation can be in-
terrupted.
Note: Always turn on the Controller and the load simultaneously.
Never turn on the load when the Controller is already turned
on. Doing so will disable proper self-tuning and optimum
control.
For example, when setting the parameters to the Controller
with the load turned off, turn off the Controller once after
completing the setting and then turn it on again simulta-
neously with the load. Or, switch event input 2 from STOP to
RUN.

Error Messages

The Temperature controller is provided with self-diagnostic functions, and will display an error message on the PV display when an error is
detected.
Message
s.err
Input error
(S.Err)
e111
Memory error
(E111)
e333
A/D converter error
(E333)
a.err
Calibration data error (displayed
(A.Err)
for 3 s when the Temperature
Controller is turned on)
Note: When the input is within the possible control range but outside the possible display range (i.e., –1999 to 9999),
the value is smaller than –1999 and
functions of the Temperature Controller will work normally.
Error
Error output status
Control output
OFF (2 mA max.)
OFF (2 mA max.)
OFF (2 mA max.)
Normal operation (accuracy not
guaranteed)
will be displayed if the value is larger than 9999, however, the control and alarm output
19
17
Open
Operation
Alarm output
Processes the
1. Check if the input is outside the possible
control range (i.e., ±10% of the set
error as an
temperature range) (see note).
abnormally high
temperature error.
2. Check if the settings of the inputs are
wrong.
3. Check if there is any wiring mistake,
wire burnout, or short-circuit.
OFF
Turn off and then turn on the
Temperature Controller. If the display
does not change then, repairs are
necessary.
necessary.
If the display returns to normal, the
OFF
Temperature Controller may have been
influenced by noise. Check if noise is
being generated.
Re-calibration is necessary.
E5jJ
19
17
Short-circuit
Operation is being
interrupted.
Item to be checked