Omron E5CN-HT User Manual page 353

Digital controllers programmable type
Hide thumbs Also See for E5CN-HT:
Table of Contents

Advertisement

PID Setting Level
Parameters
Characters
d.pid
Display PID Selec-
tion
up
PID 1 Proportional
Band
1.i
PID 1 Integral Time
1.d
PID 1 Derivative
Time
1.olh
PID 1 MV Upper
Limit
1.oll
PID 1 MV Lower
Limit
1.aut
PID 1 Automatic
Selection Range
Upper Limit
1.csc
PID 1 Cooling Coef-
ficient
1.lbr
PID 1 LBA Detec-
tion Time
2.p
PID 2 Proportional
Band
to
2.lbr
PID 2 LBA Detec-
tion Time
3.p
PID 3 Proportional
Band
to
3.lbr
PID 3 LBA Detec-
tion Time
4.p
PID 4 Proportional
Band
to
4.lbr
PID 4 LBA Detec-
tion Time
5.p
PID 5 Proportional
Band
to
Setting (monitor) value
1 to 8
Temperature input: 0.1 to
3240.0
Analog input: 0.1 to 999.9
Standard/heating/cooling,
position proportional (closed):
0.0 to 3240.0
Position proportional (floating):
0.1 to 3240.0
0.0 to 3240.0
Standard: MV lower limit (0.1
to 105.0)
Heating/cooling: 0.0 to 105.0
Position proportional (closed):
MV lower limit (0.1 to 105.0)
Standard: 5.0 to MV upper
limit 0.1
Heating/cooling: 105.0 to 0.0
Position proportional (closed):
5.0 to MV upper limit 0.1
Temperature input: 19999 to
32400
Analog input: 5.0 to 105.0
0.01 to 99.99
0 to 9999 (0: LBA function
disabled)
Temperature input: 0.1 to
3240.0
Analog input: 0.1 to 999.9
0 to 9999 (0: LBA function
disabled)
Temperature input: 0.1 to
3240.0
Analog input: 0.1 to 999.9
0 to 9999 (0: LBA function
disabled)
Temperature input: 0.1 to
3240.0
Analog input: 0.1 to 999.9
0 to 9999 (0: LBA function
disabled)
Temperature input: 0.1 to
3240.0
Analog input: 0.1 to 999.9
Display
Default
(See note 1.)
8.0
10.0
%FS
233.0
s
40.0
s
105.0
%
5.0
%
105.0
5.0
1320.0
EU
105.0
% (See
note 2.)
1.0
None
0
s
8.0
10.0
%FS
0
s
8.0
10.0
%FS
0
s
8.0
10.0
%FS
0
s
8.0
10.0
%FS
Appendix
Unit
Set value
C or F
C or F
C or F
C or F
C or F
331

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5en-htE5an-ht

Table of Contents