Omron E5CN-HT User Manual page 362

Digital controllers programmable type
Hide thumbs Also See for E5CN-HT:
Table of Contents

Advertisement

Parameters
Characters
out2
Control Output 2
Assignment
Note
(1) Displayed for ON/OFF control.
(2) The setting range depends on whether control output 1 is a linear output (current output or linear
voltage output) or an ON/OFF output (relay output or voltage output (for driving SSR)).
(3) The setting range depends on whether control output 2 is a linear output (current output or linear
voltage output) or an ON/OFF output (relay output or voltage output (for driving SSR)).
(4) WR1 to WR8 are not displayed if logic operations are not used.
340
Setting (monitor) value
When control output 2 is a
ON/OFF output (See note 4.):
NONE: No assignment
O:
Control output (heat-
ing)
C-O:
Control output (cool-
ing)
ALM1: Alarm 1
ALM2: Alarm 2
ALM3: Alarm 3
P.END: Program end output
RALM: Control output ON/
OFF count alarm
STG: Stage output
RUN: Run output
TS1: Time signal 1 output
TS2: Time signal 2 output
WR1: Work bit 1 (See note 4.)
WR2: Work bit 2 (See note 4.)
WR3: Work bit 3 (See note 4.)
WR4: Work bit 4 (See note 4.)
WR5: Work bit 5 (See note 4.)
WR6: Work bit 6 (See note 4.)
WR7: Work bit 7 (See note 4.)
WR8: Work bit 8 (See note 4.)
When control output 2 is a lin-
ear output (See note 4.)
NONE: No assignment
O:
Control output (heat-
ing)
C-O:
Control output (cool-
ing)
Display
Default
NONE
none
o
c-o
alm1
alm2
alm3
p.end
ralm
stg
run
ts1
ts2
wr1
wr2
wr3
wr4
wr5
wr6
wr7
wr8
none
o
c-o
Appendix
Unit
Set value
None

Advertisement