Omron E5CN-HT User Manual page 249

Digital controllers programmable type
Hide thumbs Also See for E5CN-HT:
Table of Contents

Advertisement

PID Setting Level
*.p
PID * Proportional Band
*.i
PID * Integral Time
*.d
PID * Derivative Time (*: 1 to 8)
Function
Setting
See
See
*.olh
PID * MV Upper Limit
PID * MV Lower Limit
*.oll
(*: 1 to 8)
Function
These parameters set the PID constants for each PID set. If auto-tuning is
executed, these parameters are set automatically.
P action:
For the P action, the MV is proportional to the derivative.
I action:
For the I action, an output is produced that is proportional to the time
integral of the derivative. An offset normally occurs with the proportional
action, so the proportional action is used in combination with the inte-
gral action. As time passes, this offset disappears and the control tem-
perature comes to match the set point.
D action:
For the D action, an output is produced that is proportional to the time
derivative of the input. Because the proportional action and integral
action correct for errors in the control result, the control system will be
slow to respond to sudden changes in temperature. The derivative
action performs a corrective action by increasing the MV in proportion to
the slope of the temperature change.
Parameter
Proportional
Temperature: 0.1 to 3,240.0
Band
Analog: 0.1 to 999.9
Integral Time
Standard/heating and cooling,
position proportional (closed): 0.0
to 3,240.0
Position proportional (floating): 0.1
to 3,240.0
Derivative Time
0.0 to 3240.0
Note If the settings for RT (robust tuning) are changed, the P (proportion-
al band), I (integral time), and D (derivative time) will be initialized.
■ Related Parameters
AT execute/cancel (adjustment level): Page 208
These parameters set the MV upper and lower limits for each PID set.
• The MV Upper Limit and MV Lower Limit parameters set the upper and
lower limits of the manipulated variable. When the calculated manipulated
variable exceeds the upper or lower limit value, the upper or lower limit
value will be the output level.
• MV limits do not operate when floating control is used with models that
support position-proportional control, so these parameters are disabled.
2-PID control must be used.
Setting range
2-PID control must be used.
Closed control must be used (for
position proportional models).
Section 5-6
Unit
Default
C or F
8.0
%FS
10.0
s
233.0
s
40.0
227

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5en-htE5an-ht

Table of Contents