Adjustment Level
See
See
hb1
Heater Burnout Detection 1
Function
Setting
See
See
oc1
Heater Overcurrent Detection 1
Function
Setting
■ Related Parameters
Heater burnout detection 1, Heater burnout detection 2 (adjustment level):
Page 211, 212
HB ON/OFF (advanced function setting level): Page 259
Heater overcurrent detection 1, Heater overcurrent detection 2 (adjustment
level): Page 211, 213
Heater overcurrent use (advanced function setting level): Page 283
Error displays ct1: Page 320
This parameter sets the current for the heater burnout alarm to be output.
• The heater burnout alarm is output when the heater current value falls
below the setting of this parameter.
• When the set value is 0.0, the heater burnout alarm output is turned OFF.
When the set value is 50.0, the heater burnout alarm output is turned ON.
Setting range
0.0 to 50.0
A
■ Related Parameters
Heater current 1 value monitor (adjustment level): Page 191
HB ON/OFF, Heater burnout latch, Heater burnout hysteresis (advanced func-
tion setting level): Page 260, 260
This parameter sets the current value for heater overcurrent alarm outputs.
• A heater overcurrent alarm is output when the heater current exceeds the
value set for this parameter.
• When the set value is 50.0, the heater overcurrent alarm is turned OFF.
When the set value is 0.0, the heater overcurrent alarm is turned ON.
Setting range
0.0 to 50.0
A
Heater burnout, HS alarms, and
heater overcurrent detection must be
supported.
Alarm 1 must be assigned.
The Heater Burnout Detection
parameter must be set to ON.
Unit
Default
0.0
Heater burnout, HS alarms, and
heater overcurrent detection must be
supported.
Alarm 1 must be assigned.
The Heater Overcurrent Use ON/
OFF parameter must be set to ON.
Unit
Default
50.0
Section 5-5
211