Parameter
Characters
Segment 0 Set Point sp
pr
Segment 0 Rate of
Rise
time
Segment 0 Time
Segment 1 Type to
Segment 1 Time
Segment 2 Type to
Segment 2 Time
to
Segment 31 Type to
Segment 31 Time
pid
PID Set No.
al-1
Alarm Value 1
al-1h
Alarm Upper Limit 1
al-1l
Alarm Lower Limit 1
al-2
Alarm Value 2
al-2h
Alarm Upper Limit 2
al-2l
Alarm Lower Limit 2
al-3
Alarm Value 3
al-3h
Alarm Upper Limit 3
al-3l
Alarm Lower Limit 3
Program Repetitions rpt
link
Program Link Desti-
nation
ts15
Time Signal 1 Set
Segment
on1
Time Signal 1 ON
Time
of1
Time Signal 1 OFF
Time
ts25
Time Signal 2 Set
Segment
on2
Time Signal 2 ON
Time
of2
Time Signal 2 OFF
Time
Adjustment Level
Parameters
Characters
l.adj
Adjustment Level
Display
at
AT Execute/Cancel
cmwt
Communications
Writing
irdr
Infrared Communica-
tions Use
spmd
SP Mode
Setting (monitor) values
Set Point Lower Limit to Set
Point Upper Limit
0 to 32,400
0.00 to 99.59
0 to 8 (0: Auto selection)
19,999 to 32,400
19,999 to 32,400
19,999 to 32,400
19,999 to 32,400
19,999 to 32,400
19,999 to 32,400
19,999 to 32,400
19,999 to 32,400
19,999 to 32,400
0 to 9,999
END ( 1) or 0 to 7
0 to 31
0.00 to 99.59
0.00 to 99.59
0 to 31
0.00 to 99.59
0.00 to 99.59
Setting (monitor) value
OFF: AT Cancel
AT-2: 100%AT Execute
AT-1: 40%AT Execute (See
note 2.)
OFF, ON
OFF, ON
PSP, FSP, RSP
Display
Default
0.0
0.0
0.00
1
0
0
0
0
0
0
0
0
0
0
end
END
0
0.00
0.00
0
0.00
0.00
Display
Default
off,
OFF
at-2,
at-1
off, on
OFF
off, on
OFF
psp, fsp,
PSP
rsp
Appendix
Unit
Set value
EU
EU/Time
Unit of
Ramp Rate
Program
Time Unit
None
EU
EU
EU
EU
EU
EU
EU
EU
EU
Repetitions
None
None
Program
Time Unit
Program
Time Unit
None
Program
Time Unit
Program
Time Unit
Unit
Set value
None
None
None
None
327