Advanced Function Setting Level
init
Parameter Initialization
Function
Setting
rest
Standby Sequence Reset
Function
258
• This parameter returns all parameter settings to their defaults.
• After the initialization, the set value automatically turns off.
Setting range
off: Initialization is not executed.
fact: Initializes to the default settings given in the manual.
• This parameter selects the conditions for enabling reset after the standby
sequence of the alarm has been canceled.
• Output is turned OFF when switching to the initial setting level, communi-
cations setting level, advanced function setting level, or calibration level.
• Condition A
At start of operation (including after turning ON power).
When the Run/Reset parameter is changed to Run.
When program is started (including when the program is started for pro-
gram repetition or link).
When the segment is changed (including when an advance is executed).
When the program number is changed.
When the SP of the current segment is changed (including changing the
fixed SP in Fixed SP Mode).
When the alarm value (alarm upper or lower limit) is changed in the cur-
rent program.
When the temperature input shift (upper/lower limit temperature input
shift) is changed.
When the program SP shift value is changed.
• Condition B
Power ON
The following example shows the reset action when the alarm type is
lower-limit alarm with standby sequence.
Alarm
(after change)
Alarm
Alarm output:
Condition A
Alarm output:
Condition B
Alarm 1 to 3 type must be 5, 6, 7, 10,
or 11.
Condition A only
SP change
Condition A
only
Section 5-10
Default
off
Alarm hysteresis
: Standby sequence canceled