Advanced Function Setting Level
alsp
Alarm SP Selection
Function
Setting
See
See
rspu
Remote SP Enable
Function
Setting
See
See
278
This parameter sets whether to use the present SP or the segment SP as the
SP that triggers a deviation alarm during ramp segment operation.
• Set the present SP or the segment SP as the SP that triggers a deviation
error.
Setting range
sp-m: Present SP, tsp: Segment SP
■ Related Information
3-12 Starting and Stopping Operation (
• When this parameter is set to ON, you can switch between a remote SP
(RSP) and program SP (PSP), or between a remote SP and fixed SP
(FSP) (PSP or FSP is set in the SP Mode parameter).
• When this parameter is set to OFF, the program SP or fixed SP is used
(PSP or FSP is set in the SP Mode parameter).
Setting range
ON: Enabled, OFF: Disabled
■ Related Parameters
SP mode (adjustment level): Page 209
Section 5-10
Alarm 1, 2, and 3 functions must be
assigned.
The alarm type must be set to 1, 2, 3,
4, 5, 6, or 7.
Default
sp-m
rtsm
): Page 89
E5AN/EN-HT Only.
Default
off