Advanced Function Setting Level
sub3
Auxiliary Output 3 Assignment
Function
Setting
See
See
csel
Character Select
Function
Setting
• This parameter sets the function to be assigned to Auxiliary output 3.
none: No function is assigned to auxiliary output 3.
o:
Heating control output is output.
c-o:
Cooling control output is output. (See note 1.)
alm1: Alarm 1 is output.
alm2: Alarm 2 is output.
alm3: Alarm 3 is output.
p.end: Program end is output. (See note 2.)
ralm: Control output ON/Off count alarm
wr1:
Work bit 1 (See note 3.)
wr2:
Work bit 2 (See note 3.)
wr3:
Work bit 3 (See note 3.)
wr4:
Work bit 4 (See note 3.)
wr5:
Work bit 5 (See note 3.)
wr6:
Work bit 6 (See note 3.)
wr7:
Work bit 7 (See note 3.)
wr8:
Work bit 8 (See note 3.)
(1) If c-o is assigned for standard control, a value equivalent to 0% will be
Note
output.
(2) Can be selected when the Program Pattern parameter is set to OFF, but
the function will be disabled.
(3) WR1 to WR8 are not displayed when the logic operation function is not
used.
■ Related Parameters
Standard or heating/cooling: Page 239 (initial setting level)
• This parameter switches the characters to be displayed.
The following two types of characters can be displayed.
11-segment display
7-segment display
on: 11-segment display, off: 7-segment display
When set to on, an 11-segment display is used.
Setting range
Setting range
Section 5-10
Auxiliary output 3 must be assigned
(E5AN-H and E5EN-H only).
Default
alm3
Default
on
277