Initial Setting Examples
Example 1 (Models with Standard or Heating/Cooling Control)
Input type:
5 (K thermocouple,
200.0 C to 1,300.0 C)
Control method: ON/OFF control
Alarm type:
2 (upper limit)
Alarm value 1:
20 C (deviation)
Set point
Segment 1
Segment 2
100. 0
50. 0
0.2 0
0.4 0
Parameter
Number of Segments Used (Program 0)
Program No.
0
Segment No.
Segment Set Point
50. 0
Segment Time (h.min)
0.0 0
Setup Procedure
Power ON
Segment 3
Initial Setting
Level
Set input
specifications
0. 20
Set control
specifications
Time (h.min)
Set alarm type
Setting
4
0
1
2
3
100. 0
100. 0
50. 0
0.2 0
0.4 0
0.2 0
Program Setting
Level
Set the programs
Set alarm values
Operation
Level
Trial operation
Start operation
Power ON
If the power supply is
turned ON before the
sensor is wired,
Operation
s.err will be
displayed.
Level
Initial Setting
Level
Check input type.
Press the UD
Keys to select
ON/OFF control.
Check alarm type.
Operation
Level
Program
Setting Level
Make sure that the
Display Program
Selection is 0.
Use the
UD Keys
to set the Number of
Segments Used.
UD Keys
Use the
to set the Display
Segment Selection.
UD Keys
Use the
to set the Segment
Set Point.
UD
Use the
Keys to set the
Segment Time.
end will be
displayed when all
segments are set.
Use the
UD Keys
to set Alarm Value 1
to 20 C.
Operation
Level
Confirm that the set
point is 50.0 C.
Set Run/Reset to
Run.
Start operation.
Section 3-1
25.0
PV/SP
c
0.0
Press the O Key for
at least 3 s.
in-t
Input Type: 5
5
M
ON/OFF
cntl
onof
For ON/OFF
control:
control, set
onof
pid
onoff.
PID
M
control:
alt1
Alarm 1 Type: 2
2
M
Press the O Key for
at least 1 s.
25.0
PV/SP
c
0.0
Press the O Key
for less than 1 s.
d.prg
Display Program Selection
0
M
No. of Segments Used changed
s-no
from 8 to 4.
4
M
d.seg
Display Segment
Selection changed
0
from end to 0.
M
Set segments 1,
2, and 3 in the
sp
c
Segment Set Point
same way.
changed from 0.0 to
50.0
50.0.
M
Segment Time
time
The default is
0.00
h.min.
M
d.seg
Display Segment
Selection
end
M
al-1
Alarm Value 1 changed
c
from 0.0 to 20.0.
20.0
Press the O Key three times
(for less than 1 s).
25.0
c
PV/SP
50.0
M
M
r-r
Run/Reset
rst to run
run
49