Operation Level
r-r
Run/Reset
Operation
o
MV Monitor (Heating)
Function
Monitor
See
See
c-o
MV Monitor (Cooling)
Function
Monitor
194
This parameter is used to start and stop operation.
Operation will start when run (run) is selected and it will stop when rst
(reset) is selected. The RST indicator will light while operation is stopped.
The default is rst.
This parameter is used to check the manipulated variable for the heating con-
trol output during operation.
• This parameter cannot be set.
• During standard control, the manipulated variable is monitored. During
heating/cooling control, the manipulated variables on the control output
(heating) is monitored.
• The default is OFF and the manipulated variable is not displayed.
Control
Standard
Heating/cooling
■ Related Parameters
MV display (advanced function setting level): Page 262
This parameter is used to check the manipulated variable for the cooling con-
trol output during operation.
• This parameter cannot be set.
• During heating/cooling control, the manipulated variable on the control
output (cooling) is monitored.
• The default is OFF and the manipulated variable is not displayed.
Control
Heating/cooling
The MV Display parameter must be
set to ON.
Monitor range
Unit
5.0 to 105.0
%
0.0 to 105.0
%
The control system must be set to
heating/cooling control.
The MV Display parameter must be
set to ON.
Monitor range
Unit
0.0 to 105.0
%
Section 5-3