Bosch D9412GV4 Program Entry Manual page 85

Table of Contents

Advertisement

D9412GV4/D7412GV4/D7212GV4
CC# Assign Door
Default:
Selection:
No Door
1 to 8
This feature is not available with the D7212GV4. Keep the default setting.
The door assigned to this keypad is used:
NOTICE!
NOTICE!
During the Add User Mode, tokens or cards, door control requests, and RTE/REX do not
function. Put the Door Mode into an unlocked state before adding users if there is heavy
activity for this door.
CC# Trouble Tone
Default:
Selection:
Yes
No
Determines whether this keypad, or any keypad with the same address setting, emits the
panel-wide trouble tones (power, phone, SDI bus, and Zonex bus).
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set CC# Trouble Tone to Yes.
NOTICE!
Panel-wide trouble tones do not include Point Troubles, Buzz on Fault, or (for D9412GV4 and
D7412GV4) Close Door Now.
NOTICE!
Assign two CCs to the same area so one keypad emits the tone and another does not.
Bosch Security Systems, Inc.
Door 1, Area 2 to 8 No Door
No Door, 1 to 8 on D9412GV4
(No Door, 1 to 2 on D7412GV4)
No door controller is assigned for adding tokens.
The door controller assigned to this keypad is used to read new door
credentials or when Dual Authentication is enabled.
To add door credentials to a user
With CC## Close Door Warning Tone to annunciate the Door Left Open warning
To enable CC# Dual Authentication for CC# Passcode Functions.
If a door is not programmed for this prompt and a door is not assigned to the area using
the D# Entry Area in the Access Control section, 9210 NOT READY appears at this keypad
when you attempt to add a user or perform dual authentication.
Assigning a door to a keypad is not necessary for the user to control the door(s) using the
Door Control function. Any door that is active can be controlled by a user who has the
appropriate door control authority. The door control functions are available to a valid
user at any keypad with access to the area where the door is assigned.
The setting of CC# Passcode Function does not affect the ability to add or change door
credentials.
Yes
Yes or No
Panel-wide trouble tones sound and visual displays show at this
keypad.
Panel-wide troubles do not sound. Visual displays still show.
Program Entry Guide
Panel and Area Wide Parameters | en
F.01U.218.312 | 04 | 2012.03
85

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7412gv4D7212gv4

Table of Contents