Bosch D9412GV4 Program Entry Manual page 68

Table of Contents

Advertisement

68
en | Panel and Area Wide Parameters
NOTICE!
For D9412GV4 and D7412GV4 Control Panels, use:
4 min for UL
5 min for ULC
Enter the number of minutes the bell rings for Burglary Alarm points. The relay activated for
this time is programmed in A# Alarm Bell in Area Relays.
The bell output begins as soon as the burglary alarm occurs. It shuts off the bell when the
programmed number of minutes expires.
When the control panel's internal clock begins a new minute, it considers the first minute
expired. Program Burg Time for 2 min or more.
NOTICE!
Check with your AHJ to determine the appropriate bell time for your geographical area.
For SIA CP-01 Compliance:
A# Burg Time must be 6 min or more.
A# Burg Pattern
Default:
Selection:
Steady
Pulse
CA Standard
TempCode3
Select the bell pattern this area uses to signal an alarm on a Non-fire point.
A# Single Ring
Default:
Selection:
Yes
No
Determines if an alarm from a non-fire point can restart the alarm bell time with each Alarm
Event, or only start alarm output once per arming period.
This does not silence the keypad alarm bell tone, or prevent any reports. This feature does not
affect Fire points. Fire points restart bell time with each new alarm.
NOTICE!
If an alarm occurs on a 24-hour point while the area is disarmed, arming that area with a key
switch does not clear the A# Single Ring flag.
F.01U.218.312 | 04 | 2012.03
Steady
Steady, Pulse, CA Standard,TempCode3
Steady Output
Pulse March Time
120 beats per minute, at an even tempo
California Standard
10 sec On + 5 sec Off + 10 sec On + 5 sec Off. This sequence repeats
until bell time expires.
Temporal Code 3
0.5 sec On, 0.5 sec Off, 0.5 sec On, 0.5 sec Off, 0.5 sec On, 1.5 sec Off;
pattern repeats. This sequence repeats for a minimum of 3 min and
with a ± 10% tolerance.
No
Yes or No
One bell output per arming period. After one alarm, alarms on any Non-
fire points in the same area cannot restart the bell until the armed state
changes. An alarm on a different point in same area restarts bell output.
Restart bell output with each alarm event.
Program Entry Guide
D9412GV4/D7412GV4/D7212GV4
Bosch Security Systems, Inc.