136 en | Points
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set this parameter to No.
NOTICE!
If you want this point to ring the bell because the message failed to reach the central station
receiver, program P## Audible After 2 Failures as Yes.
P## Ring Until Restored
Default:
Selection:
Yes
No
Use this option to determine if the bell continues to ring until the Fire Bell time expires. The
point returns to a normal condition when the user acknowledges the alarm to silence the bell.
NOTICE!
If the point restores and the fire alarm is not silenced from the keypad, the fire alarm output
continues until Fire Bell time expires. If the point does not restore, the fire alarm output
continues even after bell time expires.
NOTICE!
Use this option for fire applications to meet the requirement that audible alarms cannot be
silenced until the fault condition clears or the Fire Bell time expires.
P## Audible After 2 Failures
Default:
Selection:
Yes
No
When set to Yes, if the report fails to reach the central station after two attempts, a silent
alarm rings the A## Burg Alarm bell. A silent alarm is generated when a point with P## Silent
set to Yes is faulted while armed.
NOTICE!
When a point programmed for P## Silent Bell is faulted, the timer for the A# Burg Time starts,
even though the bell is not yet ringing. As much as 3 min can elapse before the second
attempt fails. Ensure that A# Burg Time is programmed to provide the amount of bell time you
need, minus the additional 3 min that might elapse before the bell actually begins to ring.
P## Invisible Point
Default:
Selection:
Yes
No
F.01U.218.312 | 04 | 2012.03
Refer to the program record sheet
Yes or No
The relay programmed to provide fire alarm output for this point cannot
be de-activated until the point restores to normal.
The relay programmed to provide fire alarm output for this point can be
de-activated before the point restores to normal.
Refer to the program record sheet
Yes or No
A# Burg Alarm relay activates after two failed attempts.
P## Silent points do not cause the A# Burg Alarm relay to activate even
if the report does not get to the central station receiver.
Refer to the program record sheet
Yes or No
Keypads do not display alarm activity from this point.
Activity from this point is visible at the keypads.