en | Panel and Area Wide Parameters
4.
Log % Full
Default:
Selection:
When the event log reaches the percentage full indicated in this prompt, the control panel
logs a Log Threshold event. If Contract RPS if Log % Full is set to Yes, then the control panel
will attempt to contact Unattended RPS and copy the event log before messages are
overwritten.
A setting of 0 disables the Log Threshold and Log Overflow Events. These events are not
entered in the log or reported to the central station receiver or the local printer.
The control panel continues to log events after the Log Threshold Report is sent. When the
event log reaches 100%, a Log Overflow event is generated and the oldest events are
overwritten.
The control panel does not call RPS again until it downloads the log and the Log % Full
percentage is reached. These events are also sent to the control panel's event log and to the
local printer(s) if installed.
NOTICE!
The Log Overflow Event is not sent to the central station unless Expanded Test Report is
programmed Yes.
NOTICE!
Failure to program the RPS telephone number and the RPS IP address number results in a
FAIL TO CALL RPS trouble event sent to the central station when the log threshold is reached.
Refer to Section RPS Phone #, page 58 for information about programming the RPS telephone
number. Refer to the Section Path # Network Address, page 41 for information about enabling
network RPS.
Contact RPS if Log % Full
Default:
Selection:
Yes
No
When the event log reaches the percentage full indicated by Log % Full the Log Threshold
event is put in the event log. If this prompt is set to Yes and either the RPS Network Address
or RPS Phone # are programmed, then the control panel will attempt to contact Unattended
RPS as described in Section 3.8.3 Panel Initiated Unattended RPS, page 55.
RPS Call Back
Default:
Selection:
F.01U.218.312 | 04 | 2012.03
it. The Previous and Next softkeys advance through the letter characters (A, B, C, D, E,
F).
Press the Save softkey to save the passcode. When the keypad reads Parameter Saved,
your selection has been configured.
0
0 to 99
No
Yes or No
Directs the control panel to automatically communicate with
Unattended RPS over network or phone when Log Threshold is
reached.
The control panel will not automatically contact RPS when Log
Threshold is reached.
No
Yes or No