Bosch D9412GV4 Program Entry Manual page 22

Table of Contents

Advertisement

22
en | Panel and Area Wide Parameters
Phone Supervision Time
Default:
Selection:
0
10 to 240
Phone line trouble responses: Keypads display SERVC PH LINE # to indicate which phone line
failed. The keypad initiates a trouble tone if Buzz on Fail is Yes and CC Trouble Tone is Yes.
With dual phone lines (using the D928 Module), the restored phone line handles all messages
regardless of the phone line's number.
Phone, Trouble, and Restoral Events report when they occur. They report also when a
Diagnostic Report is initiated from a keypad or by a Sked.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set this parameter to a non-zero
value.
Alarm On Fail
Default:
Selection:
Yes
No
NOTICE!
To meet UL 864 requirements, set this parameter to No.
Phone Supervision Time must be programmed to use this feature.
Phone Failure Alarm Responses: The Alarm Bell relay for Area 1 activates. All Phone Event
messages report as Area 1 and the account number for Area 1.
Buzz On Fail
Default:
Selection:
Yes
No
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set this parameter to Yes.
NOTICE!
Phone Supervision Time must be programmed to use this feature.
When Buzz on Fail is Yes, users can disable the resulting trouble tone on individual keypads
by setting CC# Trouble Tone to No.
F.01U.218.312 | 04 | 2012.03
0
0, 10 to 240
No phone line supervision.
Enter the number of seconds (in 10 sec increments) you wish to wait
before indicating trouble. After a faulted phone line restores, it takes
the same amount of time to start restoral responses.
No
Yes or No
Generate alarm responses when a phone line fails.
Phone failures report as trouble responses for Area 1 or the account
number associated with Area 1.
Yes
Yes or No
Generate panel-wide trouble tones and display PHONE FAIL # at
keypads when a Phone Fail Event occurs.
Does not generate trouble tones at keypads when a Phone Fail Event
occurs. PHONE FAIL # still displays.
Program Entry Guide
D9412GV4/D7412GV4/D7212GV4
Bosch Security Systems, Inc.

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7412gv4D7212gv4

Table of Contents