112 en | Panel and Area Wide Parameters
Points 128 and Point 248 are not accessible by this function. This is normal. These points are
used for supervising the Zonex 1 bus (Point 128) and Zonex 2 bus (Point 248).This function
allows viewing of extra points. Extra points occur under three conditions: the P### Point
Source is set to anything other than Unassigned, the P### Point Index is set to 0, and at least
two points are installed for the same Point Assignment on different Point Sources.
L## Default Text
Default:
Selection:
Function No.
34
Temporarily show the armed state of the area using control panel default text, A# AREA # IS
ON, A# NOT READY, A# AREA # IS OFF, and A# ACCOUNT IS ON.
L## Change Skeds
Default:
Selection:
Function No.
35
Change skeds that can be edited.
NOTICE!
Editing of skeds can be restricted by programming S## Time Edit? to No.
L## Invisible Walk Test
Default:
Selection:
Function No.
36
Test all points that are programmed to be invisible and that are within the scope of the
keypad without sending reports to the central station. Invisible points must be programmed
P## Invisible Point as Yes. This walk test mode can test 24-hour points and controlled points.
Invisible Test? allows the user with this L## to start an invisible walk test for all 24-hour and
controlled points in the area to which this keypad is assigned. When an invisible test is
started, one person can test invisible points without assistance.
The following features are provided with the Invisible Test Mode:
F.01U.218.312 | 04 | 2012.03
Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
- or E
Function Name
Default Text
Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
- or E
Function Name
Default Text
Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
- or E
Function Name
Invisible Walk Test
The display indicates exactly how many invisible points are assigned to the area.
Battery and bell tests do not occur during this walk test.
The keypad shows point text when invisible points are tested.
The test ends when all points are tested, or if the test times out after 10 min of no
activity.
Local event printing occurs without alarm annunciation or reports sent to the central
station receiver.
The D1255 Keypad shows a sequential count and text related to the point after each
point is activated and restored.
The keypad shows All PTS TESTED. An All Points Tested Event is sent to the central
station receiver (if programmed) when the last point is tested.
Walk Start and Walk End Reports are sent to the central station receiver for the beginning
and end of the test (if programmed in phone routing).
Program Entry Guide
D9412GV4/D7412GV4/D7212GV4
Alternate Keystroke
[COMMAND][5][7]
Alternate Keystroke
[COMMAND][5][2]
Alternate Keystroke
(Menu function only)