D9412GV4/D7412GV4/D7212GV4
Path # Network Address
Default
Selection:
0 to 255
NOTICE!
If using a network as the communication means for UL 864 Commercial Fire applications
(D9412GV4 and D7412GV4), set Path # Network Address as necessary.
Path # Network Address contains the network host name or the IPV4 address for each of the
four enhanced communication paths available.
A network address has four fields. Each field has a range of 0 to 255. For example, an IPv4
address is expressed as 110.227.64.190. Contact your network administrator to obtain the
appropriate IPv4 address or host name to contact a central station receiver. If a B420
Ethernet Communication Module is installed, then the control panel has the option to use a
host name for the Path route Network Address. For example, www.bosch.com.
Refer to Section Keypad Programming of Path # Network Address, Path # Port Number, and Path
# Poll Rate, 42 and Section Path # Poll Rate, page 41.
Path # Port Number
Default
Selection:
This prompt specifies the destination port number for each of the four enhanced
communication route path destinations.
NOTICE!
Whenever a network address or port number configured in the control panel is changed, the
central station must resynchronize the control panel's anti-replay/anti-substitution static key.
Refer to Section Keypad Programming of Path # Network Address, Path # Port Number, and Path
# Poll Rate, page 42.
Path # Poll Rate
Default
Selection:
0
5 to 65534
65535
This prompt and the next two prompts determine how the SDI Path is supervised between the
SDI device and the central station receiver(s). Do not confuse the SDI Path supervision with
the supervision of the SDI device itself (the connection of the SDI device to the control panel).
Each SDI Path can be configured to transmit a Heartbeat Poll to the central station for
supervision purposes. This ensures the integrity of the connection at all times.
NOTICE!
If using Network Addresses as the communication means for UL 864 Commercial Fire
applications (D9412GV4 and D7412GV4), program this parameter as necessary.
Bosch Security Systems, Inc.
Blank
0.0.0.0 to 255.255.255.255 or [host name]
There are four numbers for an IPV4 address. Leading zeros are not
required. A host name can be used if a B420 network communication
module is installed on the control panel.
7700
1 to 65535
0
0, 5 to 65535 sec
Disables the heartbeat poll (not recommended, refer to the first
Important Note that follows).
Enables the poll rate for the amount of time programmed here.
The maximum number of 65535 sets the poll rate to once every 24 hr.
Program Entry Guide
Panel and Area Wide Parameters | en
F.01U.218.312 | 04 | 2012.03
41