D9412GV4/D7412GV4/D7212GV4
NOTICE!
Door points must be programmed as Perimeter points. If a 24-hour point type is required for
the Door point, you can use a Perimeter point type with a point response of 9 to C. Also, the
debounce count must be set to 4 in Point Assignments.
NOTICE!
When assigning Points 1 to 8 (control panel zones), the end-of-line (EOL) resistors must be
removed from the control panel.
Also, do not enable any POPIT points, OctoPOPIT points, Octo-input points, or RF points
sharing the same point number as the Door point. Failure to do so results in extra point
trouble conditions upon reboot.
D# Interlock Point
Default:
Selection:
1 to 127, 129 to 247 The point number assigned to the Interlock point. Points 128 and 248
0
Enter the interlock point number. This point, when faulted, prevents the door controller from
allowing access upon a valid ID read or door request.
Do not assign this point to another D# Door Point. You can, however, assign it to another
controller to prevent multiple controllers from activating.
CAUTION!
The Interlock point is considered in a normal state if it is bypassed, swinger bypassed, or
forced armed. This results in normal access even if the door remains open.
D# Auto Door
Default:
Selection:
Yes
No
Use this program item to automatically unlock the door (latched, shunt, and strike) when the
entry area is disarmed. The door re-locks upon Master or Perimeter Arming the area.
NOTICE!
The unlocked state activated by Auto Door operation cannot be overridden manually.
D# Fire Unlock
Default:
Selection:
Yes
No
Use this program item to activate the relay for the door strike and shunt the door zone
automatically upon a Fire Alarm. This feature overrides a Secure Door state, Locked Door
state, Auto Door, and an Interlock Faulted point. The relay activates for all doors with this
Bosch Security Systems, Inc.
0
0 to 127, 129 to 247 (0 to 75 on the D7412GV4)
are reserved by the control panel for internal use.
No point number is assigned to the Interlock point.
No
Yes or No
When the area assigned in D# Entry Area # is disarmed, the door is in
the unlocked state. When that area is armed, the door returns to the
locked state.
Door state is not affected by the armed state of the area.
No
Yes or No
Relay activates and shunt is applied for the door contact automatically
upon a Fire Alarm.
Door remains in its current mode upon a Fire Alarm.
Program Entry Guide
ACCESS CONTROL (D9412GV4/D7412GV4) | en 197
F.01U.218.312 | 04 | 2012.03