D9412GV4/D7412GV4/D7212GV4
When initiated (either through a Fire Walk Test or the keypad's Reset Sensor? function) or
when the remote programming software (RPS) interrupts power to the device for 5 sec, a
Sensor Reset report is sent to the central station receiver.
NOTICE!
When a sensor reset occurs, the control panel does not accept alarms from any points with
P## Resettable programmed as Yes. During the 5-sec reset time, alarms from these points are
ignored.
Do not mix fire and intrusion devices on the same powered loop.
P## Alarm Abort
Default:
Selection:
Yes
No
This parameter allows points with the associated Point Index to delay a Burglar Alarm (non-
fire) event for the time period specified in the Abort Window. An alarm is aborted by
performing an alarm silence operation at a keypad showing the burglar alarm condition before
this time elapses.
When an alarm is successfully aborted, the keypad shows an optional ALARM NOT SENT
message and no event is sent or written in the control panel event log. Refer to Section CC#
Abort Display, page 87.
For SIA CP-01 Compliance:
P## Alarm Abort can be set to Yes or No.
NOTICE!
This feature does not apply to Fire Alarms or invisible point alarms.
P## Wireless Point Supervision Time
Default
Selection:
None
4 hr
12 hr
24 hr
48 hr
72 hr
A fire point follows the supervision rules if configured as a point device. Fire points have a
fixed supervision interval of 4 hours, regardless of Wireless Point Supervision Time setting. If
a Fire Point setting is Yes, then the Wireless Point Supervision Time setting must be set to 4
hours. This is an alternate supervision interval to the global System Supervision Time setting.
Refer to Section System Supervision Time, page 190.
Bosch Security Systems, Inc.
Refer to the program record sheet
Yes or No
If the point goes into an alarm condition, the system delays the alarm
report for the amount of time specified in the control panel-wide
parameter Abort Window.
If the point goes into an alarm condition, alarm reports are sent
immediately.
Refer to the program record sheet
None, 4 hr, 12 hr, 24 hr, 48 hr, 72 hr
No wireless point supervision.
Send a missing condition after 4 hr of no contact from the wireless
device.
Send a missing condition after 12 hr of no contact from the wireless
device.
Send a missing condition after 24 hr of no contact from the wireless
device.
Send a missing condition after 48 hr of no contact from the wireless
device.
Send a missing condition after 72 hr of no contact from the wireless
device.
Program Entry Guide
Points | en 145
F.01U.218.312 | 04 | 2012.03