Bosch D9412GV4 Program Entry Manual page 57

Table of Contents

Advertisement

D9412GV4/D7412GV4/D7212GV4
Yes
No
This function allows the control panel, after it verifies the RPS passcode, to provide an
additional level of security by hanging up and dialing the RPS phone number at the central
station before allowing any upload or download.
NOTICE!
When using the RPS Call Back feature, be sure to program the character "C" as the last digit in
the RPS phone number when using DTMF Dialing.
RPS Line Monitor
Default:
Selection:
Yes
No
This program item enables a control panel that shares a phone line with an answering
machine to communicate with RPS at the central station, even though the answering machine
answers the phone. You must program Answer Armed or Answer Disarmed. The control
panel must be in the correct armed state.
NOTICE!
Program this item No if it causes false seizures of the phone line or if you do not use RPS. This
indicates that a device using the same frequency tone is also using the phone line to which the
control panel is connected.
NOTICE!
If RPS Call Back is programmed Yes, the control panel hangs up the phone after the RPS tone
and a proper RPS passcode is identified. It then calls the RPS phone number.
Answer Armed
Default:
Selection:
0
1 to 15
Set the telephone ring counter to answer when all areas are master armed. If any area in the
control panel is perimeter armed or disarmed, the Answer Disarmed ring counter is used.
Bosch Security Systems, Inc.
When the control panel hears the correct RPS passcode, it hangs up the
phone, seizes the phone line, then dials the programmed RPS phone
number (refer to Section RPS Phone #, page 58). This ensures that the
control panel only communicates with RPS units connected to the
programmed phone number.
If the call is answered manually, the call back must be initiated
manually.
The RPS session starts immediately. No call back is required. The
control panel can engage in RPS sessions when called from any phone
number and a proper RPS passcode is identified.
Yes
Yes or No
Allows the control panel to communicate with RPS after the answering
machine answers the phone.
Use No if the control panel does not share the phone line with an
answering machine.
7
0 to 15
No answer.
The control panel answers the phone after the specified number of
rings when all areas are master armed.