144 en | Points
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set this parameter to Yes for all
applicable Fire points.
Use this option to make a 24-hour point a Fire point. This option makes this point the highest
priority event in the control panel when an alarm occurs for both reporting and displaying on
the keypad. Refer to Characteristics of a Fire Point Section 5.2 Point Responses, page 132.
NOTICE!
You should dedicate a fire annunciation device to all your Fire points if they are assigned to a
single area in a multiple area system. Special red keypads and annunciators with specific keys
for fire systems are designed for this type of application (D1256RB and D1257RB).
NOTICE!
Do not use the Cross point function for Fire points.
P## Alarm Verify
Default:
Selection:
Yes
No
Use this option only with Fire points to designate them for alarm verification.
When an Alarm Verification point enters into alarm, the control panel removes power to all
Resettable points for the duration programmed in A# Verify Time in Section 3.10 Area
Parameters, page 61. If the point (or another Resettable point in the area) is still faulted, or
returns to a faulted state within 60 sec after the initial verification time reset, an alarm is
generated.
NOTICE!
During a Fire Walk Test the reset time is 5 sec. The time programmed in A# Verify Time is
ignored.
P## Resettable
Default:
Selection:
Yes
No
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set this parameter to Yes for
applicable resettable points.
Use this option if this is a Powered point that requires interruption of power to reset a latched
alarm condition. The Resettable point option is typically used with smoke detectors and glass
break detectors.
F.01U.218.312 | 04 | 2012.03
Refer to the program record sheet
Yes or No
Enable alarm verification on this point.
Alarm verification points must be programmed as resettable.
Disable alarm verification on this point.
Refer to the program record sheet
Yes or No
This point is reset by the Reset Sensor? function and during the alarm
verification sequence.
This point is not resettable.
Program Entry Guide
D9412GV4/D7412GV4/D7212GV4