D9412GV4/D7412GV4/D7212GV4
Yes
No
A# Exit Tone
Default:
Selection:
Sounds an exit tone during exit delay at all keypads assigned to this area.
NOTICE!
You can turn off exit tones for individual keypads by programming the appropriate CC# 1 to 8
as No in CC# Exit Tone.
A# Exit Delay Time
Default:
Selection:
Exit delay time for this area when Master Exit or Perimeter Exit arming.
NOTICE!
Points programmed for instant alarm response generate alarms immediately, even during exit
delay. To avoid instant alarms on points adjacent to the perimeter when leaving the area,
program P## Type as 3 (Interior Follower).
For SIA CP-01 Compliance the Exit Delay Time must be between 45 sec and 255 sec.
A# Auto Watch
Default:
Selection:
Yes
No
NOTICE!
Controlled points must be programmed as P## Watch Point to generate a watch tone.
A# Verify Time
Default:
Selection:
Use alarm verification with smoke detectors to reduce the number of false fire alarms. When
Verify Time is programmed, the control panel can check smoke detector point activations
before generating alarm signals.
NOTICE!
Points are programmed individually to activate the verification feature. Refer to
Section 5.1 Point Index, page 130. Any resettable Fire point can activate alarm verification for
the area to which it is assigned. Use separate area alarm-verification relays.
To enable alarm verification on a point, program Point Index, Fire Point, Alarm Verify, and
Resettable as Yes.
Bosch Security Systems, Inc.
Point Restoral Report is not sent until the bell time expires or user
acknowledges alarm condition.
Restoral Reports are sent when point restores, regardless of bell time.
Yes
Yes or No
60 sec
0 to 600 (in 5 sec increments)
No
Yes or No
When the area is disarmed, Watch Mode turns on automatically.
When the area is disarmed, Watch Mode must be turned on or off
manually.
60
10 to 60 (in 1-sec increments)
Do not enable the Cross Point feature in point indexes designated for Fire points.
Check with your authority having jurisdiction (AHJ) to determine the maximum
verification time allowed.
Program Entry Guide
Panel and Area Wide Parameters | en
F.01U.218.312 | 04 | 2012.03