D9412GV4/D7412GV4/D7212GV4
When it reaches 100% capacity (memory logger is full and previously stored events will be
overwritten), the control panel generates a local LOG OVERFLOW event. The control panel
does not call RPS again until it downloads the log and the Log % Full percentage is again
reached. These events are also sent to the control panel's event log and to the local printer(s)
if installed.
Summary Fire
Default:
Selection:
Enter the number of the relay that activates when any Fire point in the system (P## Type 0,
P## Fire Yes) enters into alarm. This relay provides a steady output until all Fire points in the
system return to normal. Refer to Section Fire Summary Sustain, page 175 for details on
alternate operation.
Summary Alarm
Default:
Selection:
Enter the number of the relay that activates when a Non-fire point enters into alarm. This relay
provides a steady output until the alarm is acknowledged by a valid passcode, then cleared
from alarm memory with an acknowledgment at the keypad.
NOTICE!
This relay does not activate for silent and invisible alarms.
Summary Fire Trouble
Default:
Selection:
Activates when any Fire point in the control panel is in trouble, or if a Fire Supervision point is
missing. This relay provides a steady output until all Fire points restore to a normal condition.
Summary Supervisory Fire
Default:
Selection:
Activates when any Fire Supervisory point in the control panel is in a supervisory condition
(off-normal). This relay provides a steady output until all Fire Supervisory points are restored
to a normal condition.
Summary Trouble
Default:
Selection:
Bosch Security Systems, Inc.
0
0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
0
0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
0
0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
0
0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
0
0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Program Entry Guide
Panel and Area Wide Parameters | en 123