Wiring to I/O terminal block

Wire to be used
The following table describes the wire to be connected to the I/O terminal block.
When using the FPGA module as a UL listed product, use the wire listed below for wiring to the terminal block.
Applicable wire
size
Stranded wire: 0.3 to
1.5 (22 to 16 AWG)
Applicable solderless terminals
For bar solderless terminals, the products in the following table are recommended. For processing methods of the cable
terminal, such as a strip length of wire, follow the specifications of the bar solderless terminal to be used. For processing, use
a tool recommended by the manufacturer of the terminals. When using the FPGA module as a UL listed product, use the UL
listed bar solderless terminals listed below.
Terminal shape
Ferrule (with insulation sleeve)
Ferrule (without insulation sleeve)
*1 When using a solderless terminal with an insulation sleeve, select the terminal whose applicable wire size is 0.75 or smaller.
7 INSTALLATION AND WIRING
70
7.4 Wiring
Type
Length
Shielded cable
• DC output: Within 3m
• Differential output:
Within 8m
• Differential input/
output: Within 10m
• DC/differential input:
Within 30m
Model
Applicable wire
size
AI0.34-10TQ
0.34 (22 AWG)
AI0.5-10WH
0.5 (20 AWG)
AI0.75-10GY
0.75 (18 AWG)
A0.5-10
0.5 (20 AWG)
A0.75-10
0.75 (18 AWG)
A1-10
1.0 (18 AWG)
A1.5-10
1.5 (16 AWG)
Material
Copper
Bar solderless terminal
*1
tool
CRIMPFOX6
Temperature rating
Strip length of wire
75 or more
10mm
Contact
PHOENIX CONTACT GmbH & Co. KG