Setting the function setting switches
Set the following functions using the DIP switch on the front of FPGA module.
• Operation mode setting function
• CC-Link IE TSN Class setting function
• Communication speed setting function
• Lock function of FPGA download via Ethernet
• JTAG FPGA download error detection disable function
• I/O signal indication setting function
• Always write register write function
When operating the function setting switch, use a flathead screwdriver with a tip width of 1.2mm or less.
Setting method
Set each function with the function setting switch 1 to function setting switch 10.
Switch name
Function setting
switch 1
Function setting
switch 2
Function setting
switch 3
Function setting
switch 4
Function setting
switch 5
Function setting
switch 6
7 INSTALLATION AND WIRING
58
7.1 Setting Switches
Function name
MODE
Operation mode setting
function
CCIETSN Class
CC-Link IE TSN Class
setting function
LINK SPEED
Communication speed
setting function
ETHERNET
Lock function of FPGA
LOCK
download via Ethernet
JTAG
JTAG FPGA download
error detection disable
function
T-LED SHIFT
I/O signal indication
setting function
Setting details
Sets the FPGA module operation mode.
• OFF: CC-Link IE TSN communication mode
• ON: Stand-alone mode
Sets CC-Link IE TSN Class.
• OFF: CC-Link IE TSN Class B
• ON: CC-Link IE TSN Class A
By using the function setting switch 1 and the IP address/station number setting
switch together, the IP address can be initialized in unit test mode or stand-alone
mode. ( Page 57 Initializing IP address in stand-alone mode, Page 432 MODULE
DIAGNOSTICS WITH THE FPGA MODULE CONFIGURATION TOOL)
For the CC-Link IE TSN Class setting status, refer to the following.
Page 495 Function setting switch state monitor
Sets the communication speed.
• OFF: 1Gbps
• ON: 100Mbps
For the communication speed setting status, refer to the following.
Page 495 Function setting switch state monitor
Prohibits FPGA download via Ethernet.
• OFF: Enable
• ON: Prohibit (lock)
For details on the FPGA download function, refer to the following.
Page 300 FPGA Download Function
Turn on the switch when performing the FPGA download via JTAG.
Be sure to turn off the switch after the completion of the download.
• OFF: Error detection enabled
• ON: Error detection disabled
For details on the FPGA download function, refer to the following.
Page 300 FPGA Download Function
Sets the terminal block whose I/O status is to be displayed on the TERMINAL NO.
• OFF: Fix LED indication terminal block.
• ON: Change LED indication terminal block. (The LED corresponding to each
terminal block alternately lights up in every two seconds)
For details on the I/O status indicator LED setting, refer to the following.
Page 31 TERMINAL NO. LEDs setting method