Clearing Error Codes - Mitsubishi Electric NZ2GN2S-D41P01 User Manual

Cc-link ie tsn fpga module
Table of Contents

Advertisement

23.2

Clearing Error Codes

The clearing method differs depending on the classification of each error.
Classification
Major
Moderate
Minor
Module related
Communication
system
Errors can be cleared by one of the following methods.
• Clearing by input/output signals
• Clearing by Command Execution of Device Station
• Clearing with the FPGA Module Configuration Tool ( Page 123 Executing error clear)
Clearing by input/output signals
Turn on Error clear request flag (RYA).
Clearing by Command Execution of Device Station
This section describes how to clear errors by executing a command of the device station.
Operating procedure
1.
Select an FPGA module from the station list on the CC-Link IE TSN Configuration window.
2.
Open the "Command Execution of Device Station" window.
[CC-Link IE TSN Configuration]  Right click on the target FPGA module  [Online]  [Command Execution of Device
Station]
3.
Set "Method selection" to "Error clear request", and click the [Execute] button.
4.
When a window appears, click the [Yes] button.
5.
When a window appears, click the [OK] button.
6.
The FPGA module error is cleared.
23 CHECK/CLEAR ERROR CODES
452
23.2 Clearing Error Codes
How to clear an error
An error cannot be cleared.
Whether an error can be cleared depends on what the error is. ( Page 450 CHECK/CLEAR ERROR CODES)
For an error code that can be cleared, clear the error after correcting the cause of the error.
Clear an error after correcting the cause of the error.

Advertisement