6.7
Wiring of External Device and I/O Terminal Block
Wiring of spring clamp terminal block
Wire to be used
The following table describes the wire to be connected to the spring clamp terminal block.
Diameter
22 to 16 AWG
Applicable solderless terminal
The following table lists the applicable solderless terminal.
Product
Terminal shape
name
Bar solderless
Ferrule (with insulation
terminal
sleeve)
Ferrule (without
insulation sleeve)
*1 When using a solderless terminal with an insulation sleeve, select the terminal whose applicable wire size is 0.75 or smaller.
Installing or removing the terminal block
The following procedures show how to install and remove the terminal block.
■Lock and release lever positions
To make it easy to install and remove the terminal block, a three-stage positioning stopper is attached so that the lever does
not freely turn around.
When installing or removing the terminal block, turn the lever to the lock or release lever position.
View of right side of I/O module: When pulling out the terminal block
(2)
(1)
View of right side of I/O module: When insertion of the terminal block is
complete
(1)
(2)
Type
Material
Stranded
Copper
Model
Applicable wire
size
AI0.34-10TQ
0.34
AI0.5-10WH
0.5
AI0.75-10GY
0.75
A0.5-10
0.5
A0.75-10
0.75
A1.0-10
1.0
A1.5-10
1.5
Temperature rating
75 or more
Bar solderless terminal
*1
tool
CRIMPFOX6
1.
Release lever position
This lever position shows the state in which the terminal
block (1) has been completely pulled out from the I/O
module. Turn from the locking lever position to the release
lever position (2) and lift the terminal block from the I/O
module.
2.
Lock lever position
This position shows the state in which the terminal block (1)
completely fits the I/O module. Check the lock lever position
(2) and pull the terminal block lightly to check that the I/O
module completely fits the terminal block.
6.7 Wiring of External Device and I/O Terminal Block
Contact
PHOENIX CONTACT GmbH
& Co. KG
6 INSTALLATION AND WIRING
6
69