When Using the Logging Function

This section describes how to log the value of 32-bit ring counters used in the usage example of the counter control part.
In addition to the parameters set as described in the section below, set the parameters as described on this page.
Page 405 When Using the Pulse Count Function
Module parameter
The setting values of the module parameters are shown below.
Setting item
Logging function enable/disable
Logging data file storage type
CSV Format setting 0 (bit0~bit15)
CSV Format setting 6 (bit96~bit111)
CSV Format setting 7 (bit112~bit127)
FTP server IP address
Login name
Password
FPGA parameter
The setting values of the FPGA parameters to be set are shown below.
Setting item
Logging cycle timing
Logging operation mode setting
Buffer operation setting
Select logging start control
Select sampling pulses
Logging data size setting
Setting value
Enable
CSV Files
Bit, binary format
Bit, binary format
Double Word [Unsigned], decimal format
IP address of the FTP server to be used
Login name of the FTP server to be used
Password of the FTP server to be used
Setting value
1s
Storage operation mode
Linear buffer operation
Register setting value (RY3)
Logging cycle timing
256 records
14 SAMPLE CIRCUIT IN CC-LINK IE TSN COMMUNICATION MODE