Analog output wiring

Motor drive module and others
*3
GND
GND
*4
*1 For the cable, use the 2-core shielded twisted pair cable.
*2 If there is noise or ripples in the external wiring, connect a 0.1 to 0.47F capacitor (25V or higher voltage-resistant product) to the input
terminal of the external device.
*3 The external load resistance values are as follows:
Voltage output: 1k to 1M
Current output: 50 to 600
*4 Ground the shielded cable of a wire for each channel as well as the FG terminal.
*5 The FG terminal is common to analog input and analog output.
Precautions
To obtain the maximum performance from the D/A conversion function and improve the system reliability, external wiring that
is noise resistant is required. Precautions for external wiring are as follows.
• Use separate cables for the AC control circuit and the external output signals of the analog output terminal or the external
power supply to avoid effects of the AC side surges or induction.
• Do not install cables near or bundle cables with any main circuit lines, high voltage lines, or load cables for equipment other
than the programmable controller. Doing so may cause the system to be susceptible to noise, surges, or induction.
• Ground shielded wires or shielded cables based on single-point ground. However, depending on the external noise
conditions, it may be better to ground them externally.
7 INSTALLATION AND WIRING
84
7.5 External Wiring
FPGA module
E0...2 Board
DA CH0
*2
VI
COM
*1
Shield
DA CH1
VI
COM
*5
FG
FG
DAC0
Power supply
monitoring
DAC1
FPGA Board
Connector
FPGA
IOE0...2_Y2
IOE0...2_Y3
IOE0...2_Y4
IOE0...2_Y6
IOE_RSTL
IOE_DCDL
IOE0...2_Y7