Diagnostics
8.2 Diagnostic data and non-volatile SIMOTION data
● Empty lines are not permitted (an empty line will be interpreted as the end of the list).
● No distinction is made between upper-case and lower-case letters.
● It does not matter whether you use "\" or "/" in the path name.
Additional references
For detailed information about IT DIAG device and diagnostic information, see the
SIMOTION IT Ethernet-Based HMI and Diagnostic Functions
8.2.4

Deleting/restoring non-volatile SIMOTION data

Requirement
The diagnostic data and non-volatile SIMOTION data has been backed up to the
CompactFlash card, see Section Backup of diagnostic data and non-volatile SIMOTION data
(Page 359).
Procedure
As of V4.3, the non-volatile SIMOTION data is restored automatically during a module
replacement (see Section Module replacement (Page 103)). To restore the non-volatile data
manually (via an operator action), proceed as follows:
1. Insert the CompactFlash card into the new D4x5-2 (which must be switched off).
2. Set the Service selector switch to the "Delete/restore non-volatile SIMOTION data"
368
Figure 8-7
Depiction of DIAGURLS.TXT editor
setting (switch position "1").
The positions of the mode selector switch are not relevant (i.e. the set operating mode
remains unchanged).
Diagnostics Manual.
Commissioning and Hardware Installation Manual, 02/2012
SIMOTION D4x5-2