Diagnostics
8.1 Diagnostics via LED displays
Table 8- 6
Firmware
LED
RDY
DP
Yellow
Not relevant
Alternating
Table 8- 7
CX32-2 – Description of the LEDs after ramp-up
LED
Color
RDY
-
(READY)
Green
Red
Red/
green
Yellow
Green/
yellow
or
red/yellow
DP
(PROFIdrive
cyclic
operation)
Green
Red
RDY and
Red
DP
358
State
Initializing
Running
State
Off
Electronic power supply is missing or outside the
permissible tolerance range.
Continuous
The component is ready for operation and cyclic
light
DRIVE-CLiQ communication is taking place.
Flashing
Commissioning/reset
0.5 Hz
Flashing
Writing to the memory card
2 Hz
Flashing
General errors
2 Hz
Flashing
CX32-2 is ready for operation.
0.5 Hz
However, software licenses are missing.
Flashing
Firmware update of the connected DRIVE-CLiQ
0.5 Hz
components running
Flashing
DRIVE-CLiQ component firmware update complete.
2 Hz
Wait for POWER ON for the components in question.
Flashing
Component detection via LED is activated (p0124[0]).
2 Hz
Note: Both options depend on the LED state when
component detection is activated via p0124[0] = 1.
Off
Cyclic communication has not (yet) taken place.
Note: The PROFIdrive is ready to communicate when
the CX32-2 is ready for operation (see RDY LED).
Continuous
Cyclic communication is taking place.
light
Flashing
Full cyclic communication has not yet taken place.
0.5 Hz
Possible causes:
D4x5-2 does not transfer any setpoints.
During isochronous operation, no global control
(GC) or a faulty global control (GC) is transferred
by the controller.
Flashing
D4x5-2 sends faulty parameterization/configuration.
0.5 Hz
Flashing
Cyclic bus communication has been interrupted or
2 Hz
could not be established.
Flashing
Bus error - communication has been interrupted.
2 Hz
Comment
See the table below
Description, cause
Commissioning and Hardware Installation Manual, 02/2012
Remedy
Check power supply
Check
parameterization/configuratio
n data
Obtain licenses
Perform POWER ON for the
respective component
Adapt configuration between
D4x5-2 and CX32-2
Correct fault
Correct fault
SIMOTION D4x5-2