Commissioning (software)
6.5 Additional information on configuring the SINAMICS Integrated
If an error is detected during the execution of a parameter job, the error cause is signaled via
the parameter itself (no message via the fault buffer).
Causes of errors for parameter jobs
Table 6- 7
Value
10
11
12
13
14
15
16
Note
The memory card must be always remain inserted for SIMOTION D; please refer to the
SINAMICS manuals for which SINAMICS control units allow the memory card to be
removed.
Parameter p7775 is only reset automatically to 0 after the successful completion of a job.
Know-how and write protection
● Parameter p7775 is not part of the know-how protection.
● Parameter p7775 is part of the write protection. This means the parameter can only be
220
Causes of errors of the parameter jobs
Cause
Error occurred while deleting
No backup possible: Memory card is not inserted
No backup possible: Memory card is full
Backup could not be completed (e.g. memory card removed during the backup)
Restoration not possible: Memory card is not inserted
Restoration not possible: Checksum of the NVRAM data backup file is faulty
Restoration not possible: No backup available
I.e. the parameter can be read and written irrespective of the know-how.
written by the controller that configured a PZD cyclic communication with the SINAMICS
when write protection is activated (p7761 = 1).
All other write jobs are acknowledged negatively, e.g.
– SCOUT/STARTER
– For SINAMICS CUs, BOP, IOP, AOP
– Other masters that only communicate acyclically with the SINAMICS
Commissioning and Hardware Installation Manual, 02/2012