The SINAMICS Integrated is now ready for operation (RDY LED flashes green at 0.5 Hz).
The CX32-2 can be accessed online, although it has not been configured yet (RDY LED
flashes green at 0.5 Hz, DP LED is off).
1. Select "Connect online" in the CX32-2 context menu. You will then be connected to the
2. Load the parameterization to the CX32-2 and copy the parameterization from RAM to
3. Then load the parameterization from the CX32-2 back to the programming device in order
4. Repeat steps 1 to 3 for each CX32-2.
5. Save the project.
Result
The CX32-2 is now also ready for operation (RDY LED is green, DP LED is green (in RUN
mode) or flashes green at 0.5 Hz (in STOP mode)).
6.4.5.2

Loading a project created offline to the CF card

Loading a project created offline to the CF card has the advantage of being faster than a
download.
It should be noted, however, that the first system power-up will take longer, as the
SINAMICS Integrated and CX32-2 will perform one-off parameter calculations. These are
automatically backed up on the CF card.
Requirement
● You will need a card reader for the SIMOTION D4x5-2 CF card.
● Your project, including all SINAMICS Integrated and CX32-2 drive components, must
● The actual topology must correspond with the reference topology.
Procedure
1. Select "Load to file system" in the SIMOTION D4x5-2 context menu.
2. Select "Normal save" and click the "Select target" button. Select your card reader's drive
3. If a project has already been saved to the CF card, the message "Memory card file
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 02/2012
CX32-2 online.
ROM.
to back up the SINAMICS parameter calculations.
Note
Topology errors can result in a download or system power-up not being possible.
have been configured already (see Preparing for configuration (Page 196)).
and confirm with "OK".
already exists. Do you want overwrite this file?" appears. Confirm the message with
"Yes".
Commissioning (software)
6.4 Configuring a CX32-2
201