4. Once the backup is complete, you can release the button and switch off the D4x5-2.
5. Remove the CompactFlash card.
Table 8- 11
Status
Backup in progress
Backup complete
INI file in the CompactFlash card main directory
1. Use a text editor (such as Notepad) to create a file called
2. Add the following text: DIAG_FILES=1
3. Copy the simotion.ini file to the CompactFlash card main directory.
4. Insert the CompactFlash card into the switched-off module.
5. Switch the D4x5-2 on and allow the SIMOTION device to power up.
6. Once the backup is complete, switch off the SIMOTION device.
7. Remove the CompactFlash card.
Table 8- 12
Status
Backup in progress
Backup complete
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 02/2012
LED displays during backup procedure
You must use a text editor and may not use any formatting in the text.
The diagnostics data and the non-volatile SIMOTION data will be backed up to the data
carrier during power-up, provided that this is still possible and is not prevented by HW
defects, for example.
NOTICE
To suppress startup in diagnostics mode again, you must delete the
the CompactFlash card.
LED displays during backup procedure
8.2 Diagnostic data and non-volatile SIMOTION data
LED displays on the D4x5-2
STOP LED and SU/PF LED flicker yellow
RUN LED flickers green
LED displays on the D4x5-2
STOP LED and SU/PF LED flicker yellow
RUN LED flickers green
Diagnostics
simotion.ini
simotion.ini
file from
365