Assigning Parameters to and Calling the S7-Graph FB
9.7.4

Automatic or Switch to next Mode (SW_TOP)

For initial project start up or for testing a control system step-by-step, the
"automatic or step-by-step" mode can be extremely useful:
• The sequencer progresses when the transition is satisfied or when there is an
edge change from 0 to 1 at the parameter T_PUSH.
Input Parameters of the Automatic or Switch to next Mode
Parameters not listed are not mode-dependent.
Parameter
OFF_SQ
INIT_SQ
ACK_EF
S_PREV
S_NEXT
SW_AUTO
SW_MAN
SW_TAP
T_PUSH
Output Parameters of the Automatic or Switch to next Mode
Parameter
S_NO
S_MORE
S_ACTIVE
ERR_FLT
AUTO_ON
TAP_ON
MAN_ON
TOP_ON
9-14
Data
BOOL
All steps are immediately deactivated, in other
words "Sequencer Off"
BOOL
Initialize sequencer, jump to initial step
BOOL
Acknowledgment of a disturbance
BOOL
As for automatic
BOOL
As for automatic
BOOL
Request the automatic mode
BOOL
Request manual mode
BOOL
Request inching mode
BOOL
The transition switches when there is a rising
edge at T_PUSH regardless of whether the
transition is satisfied.
Data
INT
Step number, indicates the selected step
BOOL
Further active steps exist and can be indicated
in S_NO
BOOL
The indicated step is active
BOOL
Error/disturbance occurred
BOOL
The automatic mode is not active
BOOL
Inching mode is not active
BOOL
Manual mode is not active
BOOL
Automatic or switch to next mode is activated