27
28
Meridian SL-100 SE Commercial Systems Card Replacement Procedures MSL15
MCRM-S card replacement procedures 292
Load the inactive RCC2 unit by typing the following string:
>loadpm unit rcc2_unit_no
and pressing the Enter key.
where
rcc2_unit_no
is the number of the RCC2 unit busied in Step 7.
Use the following information to determine where to proceed.
If load
passed
failed
Use the following information to determine where to proceed.
If you entered this proce-
dure from
alarm clearing procedures
other
Test the inactive unit by typing the following string:
> TST UNIT rcc2_unit_no
and pressing the Enter key.
where
rcc2_unit_no
is the number of the RCC2 unit loaded in Step 23
Use the following information to determine where to proceed.
If TST
passed
failed
Return the inactive RCC2 unit to service by typing the following
string:
> RTS UNIT rcc2_unit_no
in an MCRM-S RCC2
Do
Step 25
Step 26
Do
Step 33
Step 26
Do
Step 28
Step 34
NTMX77
(continued)