Meridian SL-100 SE Commercial Systems Card Replacement Procedures MSL15
MCRM-S card replacement procedures 164
Busy the RMM by typing the following string:
>BSY
and pressing the Enter key.
Example of a MAP response:
CM
MS
IOD
.
.
.
SysB
RMM
PM
0 Quit
RMM
2 Post_
3
RMM
5
4
5 Trnsl
6 Tst
7 Bsy
8 Rts
9 Offl
10 LoadPM
11 Disp_
12 Next
13
14 QueryPM
15
16
17
18
CAUTION
Static discharge may cause damage to circuit packs
Put on a wrist strap and connect it to the frame
of the RMM before removing any cards. This
protects the RMM against service degradation
caused by static electricity.
Put on a wrist strap.
Locate the card to be removed on the appropriate shelf as
shown in the following figures.
in an MCRM-S RMM
Net
PM
CCS
.
.
1ManB
ManB
OffL
4
0
10
0
0
1
ManB
NT2X11
(continued)