ASDA-B3
Tuning
5.3.6 Setting the command response gain (response)
Use P2.089 to adjust the command response gain. Increasing the gain can minimize the
5
deviation between the position command and command response in the intermittent duty zone.
This function is only available for changing commands. Before adjusting the value of P2.089,
first enable the two-degrees-of-freedom control function (set P2.094 [Bit 12] to 1).
Position
Position
Command
Command
Response
Response
Feedback
Feedback
Time
Time
Smaller
Greater
Figure 5.3.6.1 Adjust the command response gain
5-19