Temperature specifications
Table 25. Temperature specifications
Temperature
Storage
Continuous operation (for altitude less than 950 m or 3117 ft)
Expanded operating temperature
Maximum temperature gradient (operating and storage)
NOTE:
Some configurations require a lower ambient temperature for more information, see the
temperature
specifications.

Particulate and gaseous contamination specifications

Table 26. Particulate contamination specifications
Particulate contamination
Air filtration
NOTE:
This condition applies only to data center environments. Air filtration requirements do not apply to IT equipment
designed to be used outside a data center, in environments such as an office or factory floor.
NOTE:
Air entering the data center must have MERV11 or MERV13 filtration.
Conductive dust
NOTE:
This condition applies to data center and non-data center environments.
Corrosive dust
Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE:
This condition applies to data center and non-data center environments.
Table 27. Gaseous contamination specifications
Gaseous contamination
Copper coupon corrosion rate
Silver coupon corrosion rate
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.

Maximum vibration specifications

Table 28. Maximum vibration specifications
Maximum vibration
Operating
130
Technical specifications
Specifications
–40°C–65°C (–40°F to 149°F)
10°C–35°C (50°F to 95°F) with no direct sunlight on the
equipment.
For information about expanded operating temperature, see
Expanded Operating Temperature section.
20°C/h (68°F/h)
Specifications
Data center air filtration as defined by ISO Class 8 per ISO
14644-1 with a 95% upper confidence limit.
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
Air must be free of corrosive dust.
Specifications
<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-2013
<200 Å/month per Class G1 as defined by ANSI/
ISA71.04-2013
Specifications
0.26 Grms at 5 Hz to 350 Hz (all operation orientations).
Standard operating