NOTE:
*165 W and 150 W FO includes Intel Xeon Gold 6146 and 6144 processors.
Ambient temperature limitations
The following table lists configurations that require ambient temperature less than 35°C.
NOTE:
The ambient temperature limit must be adhered to ensure proper cooling and to avoid excess processor throttling, which
may impact system performance.
Table 34. Configuration based ambient temperature restrictions
System
Front Backplane
10 x 2.5 inch SAS/
PowerEdge R640
SATA hard drives
8 x 2.5 inch SAS/SATA
hard drives
4 x 3.5 inch SAS/SATA
hard drives
10 x 2.5 inch SAS/
SATA and NVMe
drives(4, 8, or 10)

Particulate and gaseous contamination specifications

The following table defines the limitations that help avoid any equipment damage or failure from particulate and gaseous contamination. If
the levels of particulate or gaseous pollution exceed the specified limitations and result in equipment damage or failure, you may need to
rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
Table 35. Particulate contamination specifications
Particulate contamination
Air filtration
Conductive dust
Corrosive dust
42
Technical specifications
Processor Thermal
Processor Heat Sink Fan Type
Design Power
200 W, 205 W
2 pipe 1U high
performance
165 W, 200 W, 205
2 pipe 1U high
W
performance
Specifications
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a
95% upper confidence limit.
NOTE:
filtration requirements do not apply to IT equipment designed to be
used outside a data center, in environments such as an office or
factory floor.
NOTE:
MERV13 filtration.
Air must be free of conductive dust, zinc whiskers, or other conductive
particles.
NOTE:
environments.
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less than
60% relative humidity.
High performance
fan
High performance
fan
This condition applies to data center environments only. Air
Air entering the data center must have the MERV11 or
This condition applies to data center and non-data center
Ambient Restriction
30°C
30°C