24.3 HR 410 Portable Handwheel
24.3.1 Checking the Keys
The keys cannot contact any more (defective contact, line, etc.) or are in continuous contact
(adhesion of the key by strong contamination, jammed chips, etc.).
With the PLC diagnostic functions TABLE or LOGIC DIAGRAM you can check the function of the
handwheel keys my means of the corresponding PLC inputs:
MP7645 determines whether the handwheel keys are evaluated by the NC or the PLC.
Evaluation of the keys via the NC. --> MP7645.0 = 0
All keys are evaluated by the NC except the keys A, B and C!
24 – 396
Press EMERGENCY STOP.
Call the table with the PLC inputs or start the logic diagram.
--> see "PLC Diagnosis" on page 10 – 73.
Press the handwheel keys.
Check whether the corresponding inputs change to 1.
X
Y
Z
Low feed
Medium
High feed
rate
feed rate
–
O109
O110
I173
I174
HEIDENHAIN Service Manual iTNC 530
IV
V
rate
+
O111
I175