25.2 Touch Trigger Probe with Cable Connection for Workpiece Setup and Measurement

Possible
causes of error
Control of the LEDs
Red LEDs on the TS 220 signalize, that the stylus is deflected:
Short
functional test
The probe to be investigated must be located inside the spindle.
May 2006
Collision (probe damaged, etc.)
Humidity
Defective cable of probe
Defective interface of probe on MC
Note
After a collision, check the accuracy of the touch probe. Ask the machine manufacturer or
your HEIDENHAIN service agency!
DANGER
Ask the machine operator and regard the machine manufacturers's safety instructions
(setup mode, etc.)!
Call the logic diagram and enter the operands M4050 and M4051.
Set the trigger to M4051. --> see "The LOGIC Diagram" on page 10 – 82.
Begin recording.
Check marker 4050. If the probe is ready, this marker has the status zero!
Deflect the stylus manually.
Check marker 4051. If the stylus is deflected, this marker changes to one!
25 – 403