16.6 Restore

When restoring, the backup of a machine (e.g., PLC data, TNC data, "full backup") are restored
from an external data medium (e.g., service laptop) to the control's hard disk.
Connection setup
Select backup file
16 – 266
Caution
When restoring the hard-disk data, the machine must not operate!
The control should be in Power interrupted state.
Never press any key on your control while data transfer is running!
Note
If you work with Ethernet connection, please check the necessary settings or reset them. -
-> see "Connection Setup" on page 16 – 247.
Tip: For the original settings for DEFINE NET, refer to file IP4.N00 that can be extracted, e.g.,
from the backup file of the corresponding machine. --> see "Extracting Files from the
Backup File" on page 16 – 265.
Set up a connection to the iTNC 530 by means of the TNCremoNT
--> see "Connection Setup" on page 16 – 247.
If this does not work, please check the connecting cable and the settings!
In the upper screen half (laptop/PC contents), select the directory where you have stored the
backup file.
In example C:\Backup machine. --> Double click the requested directory.
--> The path information appears in the blue bar atop.