Error
The corresponding PLC outputs do not function. Depending on the PLC program of the machine
manufacturer, corresponding PLC error messages are displayed.
Functional control
Ensure that:
If this is not the case.
May 2006
Note
Monitoring the PLC outputs. --> see "The TABLE Function" on page 10 – 76.
The green LEDs on X6 pin9 and pin10 of the I/O modules PLD16-8 are lit.
The green LED POWER ON on the basic module PLB 510 is lit.
Measure whether the 24 V supply voltages are available as indicated above.
Note
If the LEDs are not lit up, despite available power supply, the basic module PLB 510 or the
corresponding I/O module PLD 16-8 is probably defective.
14 – 229