Symmetricom TimeProvider 1100 Reference Manual page 145

Edge clock tl1 reference guide
Hide thumbs Also See for TimeProvider 1100:
Table of Contents

Advertisement

Table B-1. Alarms (Continued)
Alarm ID
Alarm Condition
or
Description
CONDTYPE
CLKHOLD
The local oscillator on
the specified IOC is in
Holdover Mode.
CLKFREE
The local oscillator on
the specified IOC is in
Free-run mode.
CLKWARM
The local oscillator on
the specified IOC is in
Warm-up mode.
SYNTHEOR The synthesizer
generating the modules
stable output frequency
has reached the defined
End-of-Range for the
type of oscillator used
on the IOC.
IMC2COMM A communication alarm
with the IMC module
and IOC2 module.
IOC2TO
A communication alarm
1COMM
from IOC2 module to
IOC1 module.
IOCFAIL
A summary alarm for
IOC BIST faults.
BTBCKUP
All BesTime Backup
sources, inputs are
unusable to the
BesTime engine.
CLKBRDG
The local oscillator on
the specified IOC is in
Bridging Mode.
CLKHOLD
The local oscillator on
the specified IOC is in
Holdover Mode.
CLKFREE
The local oscillator on
the specified IOC is in
Free-run mode.
097-58001-01 Revision E – September 2006
Error
AID
Service
Delay
Type
Affecting
Default
EQPT SA
IMMED
EQPT SA
IMMED
EQPT SA
IMMED
EQPT SA
IMMED
<aid> = IOC2
EQPT NSA
IMMED
EQPT NSA
IMMED
EQPT SA
IMMED
EQPT NSA
IMMED
EQPT NSA
FLT
DELAY
EQPT SA
IMMED
EQPT SA
IMMED
Appendix B Alarms
Alarm Default
Error
Level
Delay
Editable
SSU PRS SUB
NO
MJ
MJ
NO
MJ
MJ
NO
MN
MN
NO
MJ
MJ
NO
MN
MN
NO
MN
MN
NO
MJ
MJ
NO
NA
NA
NO
NA
NA
NO
MJ
MJ
NO
MJ
MJ
TimeProvider TL1 Reference Guide 145